Zeta IN8 Infinity 8 Zone Conventional Fire Alarm Panel
The Infinity 8 control panel is housed in the most attractive, modern designed, flame retardant ABS enclosure, utilising a switch mode power supply. It has a fully removable front cover which improves ease of access for cable installations.
Key Features:
- Access via password – removes problem of lost keys
- One-man test facility
- Disablement facility for zones & sounders
- Space for up to 3Ah batteries
- Sounder delay option 4 sounder circuits (IN4, IN6 & IN8)
- Sounder circuits 3 and/or 4 can be configured as Aux 24V supplies
- Meets all requirements of latest EN54 part 2 and part 4
- Internal switch-mode power supply (EN54-4 A2)
- Sounder delay option
- Selectable auxiliary supply output
Specification:
Basic Information | ||
Model | IN8 | |
Part No | 37-654 | |
Mains Voltage | 230V AC +10% / -15% @ 50/60 Hz | |
System Voltage | 24V DC (Nominal) | |
Zone Voltage | 21V DC (Nominal) | |
Sounder Alarm Output | 4 x 150mA @ 24V DC | |
Fault Relay | 1 x Volt Free Relay, SELV @ 1A Max | |
Zone Capacity | 32 devices per zone | |
Remote sounder operation | Via N/O contact connected to Class Change | |
Sounder Activation Delay | 0 to 10 minutes in 1 minute increments | |
Zone End of line | 1N4002 Diode (Cathode Stripe to Zone +ve) | |
Sounder End of Line | 10K resistor | |
Charger Voltage | 27.6V | |
Battery cut off | Battery voltage less than 20V | |
Battery Internal Resistance limit | 0.9 ohm | |
Enclosure size | 371 x 302 x 93 (mm) | |
Weight | 3 kg (Excluding Batteries) | |
Maximum battery space | 2 x 3.4 Ah, 12 Vdc sealed lead acid |