Conventional Fire Alarm Panel
Specification:
Basic Information | ||
Compatibility | Designed to comply with the requirements of BS5839-4 (for head-out monitoring use 1 x BF378M module on the EFP1’s zone circuit). | |
Mains supply | 230V 50/60Hz. | |
Internal power supply | 27V nominal. | |
Total output current limited to | 400mA @ 230V. | |
Quiescent current | 40mA (with no mains supply, detector and sounder EOLs fitted, no other loads supplied by panel). | |
Max battery size and type | 2 x 12V 2.3Ah VRLA connected in series. | |
No. of detector zone circuits | 1 (Max. length per circuit is 500m). | |
Call point resistor value | 470 to 680Ω. | |
Max. devices per detector zone | 20 detectors (max. detector current 2mA). No limit for manual call points. | |
No. of conventional sounder circuits | 2 (Max. length per circuit is 500m). | |
EOL resistor value | 6800Ω 5% Tol. 0/25W (blue, grey, red, gold). | |
Max. sounder output current | 400mA (to all outputs). Outputs are fused at 400mA. | |
Open collector outputs | Available via optional expansion loom FF380X. | |
Auxiliary inputs | Available via optional expansion loom FF380X. | |
Indicators | Mains on; Zone Fire; Zone Fault; Sounder Fault; Battery/PSU Fault; O/C Zone Fault; S/C Zone Fault. | |
Controls | External (key switch activated): Reset; Silence Alarm/Fault Sounders; Evacuate. Internal: Revert to S/C equals Fire. | |
Product dimensions (mm) | 271 W x 200 H x D 70mm. | |
Construction & finish | Metal lid and base. | |
IR Rating | IP30. | |
Weight | 2.3kg | |
Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95% |